Smoke Management System Inspection & Test Plan

ITP for mechanical smoke management systems covering smoke exhaust fans, stair pressurisation, automatic opening vents, controls integration and commissioning per AS 1668.1.

12 checklist items
3 hold points
2 witness points
Use this template — it's free

Checklist Preview

Smoke Exhaust System

Requires sign-off
P/F
Exhaust fan rated for high temperature operation
P/F
Smoke exhaust ductwork fire-rated
P/F
Exhaust volume per fire engineering report
Hold
P/F
Make-up air provisions adequate

Stair Pressurisation

Requires sign-off
P/F
Pressurisation fan duty per design
P/F
Door pressure differential within 50Pa limit
Hold Witness
P/F
Door opening force ≤ 110N
P/F
Pressure relief provisions operational

Controls & Commissioning

Requires sign-off
P/F
Interface with fire indicator panel verified
Hold Witness
P/F
Cause and effect scenarios tested
P/F
Automatic opening vents operational
Aa
Commissioning report reference