Fire Door & Smoke Door Inspection & Test Plan
ITP for fire-rated and smoke door installation covering frame fixing, door leaf installation, hardware, intumescent seals, hold-open devices and operational testing per AS 1905.1.
12 checklist items
3 hold points
2 witness points
Checklist Preview
Frame Installation
Requires sign-offP/F
Frame material and FRL per door scheduleP/F
Frame fixed plumb, level and squareP/F
Frame-to-wall gap sealed with fire sealant Hold
Door Leaf & Hardware
Requires sign-offP/F
Door leaf FRL matches schedule Hold
P/F
Fire door identification tag affixedP/F
Intumescent and smoke seals installedP/F
Door closer adjusted for full positive latchingP/F
All hardware fire-rated and compatibleOperational Testing
Requires sign-offP/F
Door self-closes and latches from any position Hold Witness
P/F
Hold-open device releases on fire alarm signal Witness
P/F
Gap clearances within AS 1905.1 limitsP/F