Fire Detection System Inspection & Test Plan

ITP for fire detection and alarm installations covering detector selection, spacing compliance, sounder coverage, FIP programming and cause-effect matrix verification per AS 1670.1.

12 checklist items
2 hold points
2 witness points
Use this template — it's free

Checklist Preview

Detection Devices

Requires sign-off
P/F
Detector types per zone requirements
P/F
Detector spacing per AS 1670.1
P/F
Mounting height and clearances compliant
P/F
MCPs at exits and travel distance compliant

Notification Devices

Requires sign-off
P/F
Sounder coverage verified by walk test
Witness
P/F
Visual alarm devices in required locations
P/F
Speaker intelligibility satisfactory (if EWIS)

Panel & Cause-Effect

Requires sign-off
P/F
FIP programmed per cause-effect matrix
Hold Witness
P/F
All zones tested and responding correctly
Hold
P/F
Brigade signalling verified
P/F
Ancillary functions tested (lifts, doors, HVAC)
As-installed drawings provided